211amps if everything runs
148amps planned
63amp gap to close
β‘ The Load List
| Qty | Item | Amps each | Total (all on) | Planned |
| 10 | Midea 8k A/C | 8 | 80 | 64 |
| 2 | Cold box A/C | 4 | 8 | 8 |
| 1 | Lights | 10 | 10 | β |
| 3 | Household refrigerators | 4 | 12 | 12 |
| 1 | Deep freeze | 4 | 4 | 4 |
| 3 | Pumps | 2 | 6 | 2 |
| 2 | RVs on camp power | 20 | 40 | 32 |
| 2 | Fans | 3 | 6 | 6 |
| 1 | Microwave | 15 | 15 | β |
| 1 | Coffee pot | 10 | 10 | β |
| β | Interactivity | 20 | 20 | 20 |
| Total | | 211 | 148 |
π° 2026 Power Pricing (per amp)
| Amps | Price | $/amp |
| 20 | $1,600 | $80 |
| 30 | $2,400 | $80 |
| 40 | $3,200 | $80 |
| 50 | $4,000 | $80 |
| 70 | $5,500 | $79 |
| 100 | $7,500 | $75 |
| 130 | $9,500 | $73 |
| 190 | $13,500 | $71 |
| 230 | $16,000 | $70 |
| 280 | $19,500 | $70 |
| 330 | $23,000 | $70 |
Sheet note: cables hook to 70A breakers; 20 ACs would split 10 per cable.
π’ The Honest Read
- The 63-amp gap is mostly lights, microwave, coffee β things that don't run 24/7. Duty cycling closes most of it.
- Stagger the big draws: microwave/coffee only when ACs are at low cycle; cold box ACs run at night when living ACs rest.
- RVs at 20A each are the fattest line β confirm they actually need camp power vs their own gen.